FixGridSouth

FixGrid+ South

(long side clamping)

(short side clamping)

INSTALLATION MANUAL

NOTE ON USE OF ROOFS WITH SUBSTRATE OR GRAVELLED COVERING

For roofs with substrate or gravel covering, it must be considered that a low weight

load for the system can only be achieved if sliding of the system sections is reliably

prevented by an adequately slip-free connection for the substrate surface. For gravel

roofs, flush embedding of the base beams in the gravel surface is enough. For overgrown

roofs, slip resistance can be achieved with additional measures. For example,

screws in the continuous beam can be used on the construction site to create a nonslip

connection to the substrate.

INSTALLATIONMANUALFORSIMPLEALIGNMENT()

TOOLSNEEDED

Tape measure,screwdriverwithTXdriveT40bit(moduleassembly)andsocketwrenchwith SW8socket

(Windsafeinstallation)

OTHERNECESSARYDOCUMENTS

Generalinstallation manual–Installationandprojectplanning

InstallationmanualRapid16moduleclamps

ProductsheetFixGrid kit

FASTENINGTORQUES

M8screwfittings:15Nm

Exception:Self-drillingscrewsmustbescrewedoninthe directionofthe endstop.

SAFETYINSTRUCTIONS

Thesystemmustbeinstalled with ballastaccordingtoload getthiswith the system

planfromthe Schletterconfiguration tool.

Breakhazard!PVmodulescanbedamagediftheyareentered.

Planningofthe solarpowersystem,installation andcommissioningmustbedoneonly byqualified

erexecutioncandamagethe systemandendangerpeople.

Electricalcurrenthazard!Installationandmaintenanceofthe PVmodulemustbedoneonly byqualified

e PVmodulemanufacturer’ssafetyinstructions!

Fallinghazard!Duringallworkonthe roof,andwhenclimbingupanddown,thereis ariskoffalling.

Alwaysobeythe accidentpreventionregulationsanduseappropriatefallprotectionequipment.

Injuryhazard!People hazardarea,beforestartinginstallation,set

upbarriersandwarnpeople inthe area.

2

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

INSTALLATIONINSTRUCTIONS

Makesuretheflatroofsealandtheinstallationsystemarecompatible.

Roofdrainagemustbeincorporatedintothesystemplan.

Forveryunevenroofsorroofseals,compensationmeasuresmayneedtobetaken

toensureevenloading.

Thenecessarygapsfromtheroofbordersmustbemaintained.

Themaximumfieldtypedependsonthetypeofroof.

Forfilmroofs,itisnomorethan10m,andforconcreteroofs,thiscanbeevenlargerinsome

cases.

Forroofswithasubstrateorgravelcovering,itmustbeensuredthattheconnectionisslip-resistant

enough.

Checktheexistinginclineoftheroofandwhethertheinstallationsystemneedstobesecuredagainst

slipping.

Thesurfaceloadmustnotexceedthebuilding'sremainingloadcapacity!

Thepartialsurfacepressureexertedunderthebaseprofilesandtheroofcladdingandinsulationmust

neverexceedthemaximumpermissiblesurfacepressure.

Currentcountry-specificlawsandregulationsmustbefollowed!

Roofcleaning!Toensureflatsupportofthebaseprofile,contaminationlikemoss,leaves,dirt,stones,

etc.,absolutelymustberemoved.

Ifthereisalightningprotectionsystem,determinetowhatextentacertifiedlightningprotection

ldalsobecheckedwhethertheinstallationchangesthelightning

protectionrequirements.

Forstaticreasons,installingasinglerowofmodulesisnotpermitted.

Beforeinstallation,theroofmustbecheckedforalltypesofdamage—especiallywatercreasing

houldbedocumentedwithphotostoprotectagainstthird-

partyclaims.

Thesystemisdesignedformoduleswithawidthof950–1050mm(typicalmoduledimensions

accordingtothecurrentstateoftheart).Othermoduledimensionsareavailableuponrequestand

ethemanufacturer'sinformationonmoduleclamping.

TheFixGrid18mountingsystemisfixedtotheroofpurelywithballast(exceptspecialcases).

Adetailedballastcalculationcanbefoundintheproject-relatedplanningdocuments.

Theballastingiscalculatedinsuchawaythatsliding,tiltingandliftingoftherackisavoided.

InstallonlyoriginalSchlettercomponents!

Nomodificationstothemodulearerequiredtosecurethem.

Allothermarkings,informationonthe numberofmodulesand

additionalinformationcanbefoundinthe project-specific

documents.

Usethe currentinstallation manual!

Canbefoundatourwebsite:

he FixGrid18 area.

3

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

FixGrid South

(Short side clamping)

TECHNICALDATA

•ConformstoUL2703

•CertifiedtoLTRAE-001

•Fireclassresistancerating:ClassA

whenusedwithtypeIphotovoltaic

modules

NGBASEPROFILELENGTHSANDMODULESUPPORTGAPS

Thelengthofthebaseprofiledependsontheselectedshadowingdistanceversusthemodulewidthandthe

dowingdistancecanbecalculatedusingtheconfigurationtool.

Distance"a"between“systemprofilebottom”and“systemprofiletop”isfixedasshownbelow:

Forversion5:863mm (front of lower rail to front of rear rail)

For version 10: 900mm (front of lower rail to front of rear rail)

Forversion13:895mm (front of lower rail to front of rear rail)

Thefirsisruleis

followed,themoduleframewidthalwaysclosesflushwiththeRapid16moduleclamps(bottomandtop).

Thebaseprofilelengthcanbeselectedfromthesixstandardlengths(2150,2650,3150,4200,6000,6300mm)

s,thebaseprofilescanbeconnectedtotheinternalconnector,itemNo.

imumpermissiblefieldsizemustbeobserved!

VERSION5:

VERSION10:

VERSION13:

4

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

FixGrid+ South

(Long side clamping)

TECHNICALDATA

•ConformstoUL2703

•CertifiedtoLTRAE-001

•Fireclassresistancerating:ClassA

whenusedwithtypeIphotovoltaic

modules

NGBASEPROFILELENGTHSANDMODULESUPPORTGAPS

Thelengthofthebaseprofiledependsontheselectedshadowingdistanceversusthemodulewidthandthe

dowingdistancecanbecalculatedusingtheconfigurationtool.

Distance"a"between“systemprofilebottom”and“systemprofiletop”isbasedonmodulewidth.

(seebelow):

Thefirsisruleis

followed,themoduleframewidthalwaysclosesflushwiththeRapid16moduleclamps(bottomandtop).

Thebaseprofilelengthcanbeselectedfromthesixstandardlengths(2150,2650,3150,4200,6000,6300mm)

s,thebaseprofilescanbeconnectedtotheinternalconnector,itemNo.

imumpermissiblefieldsizemustbeobserved!

VERSION5:

VERSION10:

5

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

Installationtimescanbeoptimizedbypre-assembling

arowofbaseprofilessidebysideonassemblystands with the

installation supports.

LATIONOFTHEMODULESUPPORTWITHPRE-ASSEMBLEDONE-TURN

CONNECTORONTHEBASEPROFILE

Markingforthe mountingofthe modulesupport:

Frontedgeofthe modulesupport=Distance-28mm

Placethe frontedgeofthe supportonthe mark;payattentiontothe directionofrotation!

Turnclockwiseby90°.

3. EXTENSION OF THE BASE RAILS

Insert splice section 150mm into the base rail as shown below.

Secure splice in place using self drilling screws provided, 1 per base rail per splice.

Observethe suitable moduleandrowdistancesforprofileandmoduleinstallation.

6

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

LATIONOFTHESTRUCTUREPROTECTIONMAT

Adherethestructureprotectionmat(300/110/20mm)afterremovingtheprotectivefilmonthebase

ethe structureprotectionmat'sminimum30mmexcesslengthatthe profileends.

min.

30mm

Thestructureprotectionmatinstallationdistancesbelowthebaseprofilearebasedontheselectedin-

stallationversion.

VERSIONA:

Place20mmthick,300mmlongstripscentrallyunderundereachsupport.

Loadplacementonsmallsurface(forlightloadsand/orfirmsubstrate)

Underimpactfromthe baseprofiles,an additionalstructureprotectionmatshouldbepositioned!

Fortransverseflowingroofwater,almostunhindereddrainageis possible.

Thepermissible surfacepressureofthe roofmustbechecked!

Adequatedrainageofprecipitation watermustbeensured!

min.30mm

300mm

300mm

obligatorycenteredbelow

bearing

7

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

VERSIONB:

Place 20 mm thick, 300 mm long strips with a distance of 100 mm between them.

Load distribution on a large surface (for high loads and/or soft substrate with low

permissible surface pressure).

Also suitable for transversely draining roof water.

Thepermissible surfacepressureofthe roofmustbechecked!

Withtransversedrainingprecipitationwater,stbe

measuredonsiteaccordingtothe localpre-cipitationquantity.

NGTHEBASEPROFILES

(Before base rail placement all gravel is to be cleared for flush placement on the roof)

•Alignthe baseprofilesparalleltoeachother,the FixZsystemprofilealignedandatarightangletothe

baseprofilesonthe substrate.

•Distanceg=Modulelength+23mm

GTHEFIRSTMODULE

ick

theRapid16middleclampwithagenerousgap,sothatthemodulecanbeinserted

betweenthe clamps.

PlacethemoduleontheFixZsystemprofileandaligntheloweredgewiththe

ethemodulealignmentaccordingto

the modulerow.

8

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

Torque Value for Rapid16 clamps = 15 N.M/11 FT-LBS

6. INSTALLINGTHEFIRSTMODULE

Placeandtightenthe endclamps (bottomandtop)onthe module,fastenwitM8(T40)screws.

Placethe centralmoduleclamponthe modulebutdonottighten.

Connectthe modulecable accordingtothe plan.

lingfurthermodules

Installinganothermodule.

Tightenthe middle clamps (bottomandtop)betweenthe moduleswith M8screws(T40).

Pre-installfurthermiddle clamps onthe freesideofthe module.

Connectthe modulecable accordingtothe plan.

Repeatthe stepsinorderuntilthe lastmodule.

INSTALLINGTHELASTMODULEOFTHEROW

Placethe lastmodule

Tightenthe middle clamps (bottomandtop)betweenthe moduleswith M8screws(T40).

Installthe endclamps onthe freesideofthe moduleandtighten.

Connectthe modulecable accordingtothe plan.

9

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

Insertendclamps atleast30mmfromthe endofthe profile.

min.30mm

Observethe moduledistanceformiddle clamps.

1-2mm

1-2mm

LINGWINDSAFES

Foreachinclinevariant,therearetwolengthtypesfor Windsafesheets:

VERSION5°:

length1750mmformodulelengthupto1700mm

length2150mmformodulelengthupto2067mm

Deliverystateas double element:pre-punchedinthe middle

is brokenapartintoindividualpartsatthispre-punching!

10

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

VERSION13°:

length1750mmformodulelengthup to1700mm

length2150mmformodulelengthup to2067mm

TheWindsafesofthe5versionarefastenedwithoneself-drillingscrew,andthe10&13versions

with2selfdrillingscrewspermodulesupport.

Viewedfromtheback,s,thefirstWindsafemust

beplacedonthebaseprofileanddistributedonthetwosupports.

Withthinsheetmetalscrews,theWindsafeisscrewedonthroughthetwoholes(13version)onthe

rightsideontotheupperFixZsystemprofile.(5versionwithonlyonescrew)

PlacefurtherWindsafesonthebaseprofile,alignthemlaterally,andscrewthemontotherightthrough

theholesoftheupperWindsafe,tWindsafeonthe

leftsidemustbefastenedwithtwothinsheetmetalscrewsatthesameheight.

OneWindsafeis fastenedwith twothinsheetmetalscrewsperside.

(10 & 13version,with 5versionwith only onescrewperside)

11

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

Windsafesare to

themodulefield,inmanycasesnoWindsafesare necessary.

LINGTHEBALLAST

Therearebasically 4possibilitiesforballastinstallation:

Ballastwith concretestones100 mmwideonthe baseprofiles(seedetailA)

Ballastwith additionaltroughs(seedetailB)

Ballastwith standinglawnedgingstonesontheWindsafe(seedetailC,for13°versiononly,

securingthe stonesagainsttipping overis recommended)

Ballastwith additionalballastshafts (seedetailD)

orballastfromacombinationofthe fouroptions

ABCD

TheinformationonballastcanbetakenfromthesystemplanfromtheSchletterconfiguration

tool.

Fastenthestructureprotectionmatpiecestotheadditionaltroughswiththefasteningflaps.

(Ballastdoesnotcomewithdelivery.)

12

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

BALLAST EXAMPLES FIXGRID 5 SOUTH:

BALLAST EXAMPLES FIXGRID 10 SOUTH:

13

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

BALLAST EXAMPLES FIXGRID 5 + SOUTH:

BALLAST EXAMPLES FIXGRID 10 + SOUTH:

14

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

detailA:

detailB:

detailC:

detailD:

Ballastwithadditionalballastshafts(detailD)

Iftheballastshaftsarefilledwithgravel,thengravelrun-outattheendsoftherowscanbepreventedby

s,theendsoftheballastshaftsmustbefoldedattheperforation.

Thefirstballastshaftisplacedfromtherightwiththerecessesandupstandonthebaseprofiles.

Allothershaftsareturned180degrees(leftrecesses)is,theshaftalwayslieswith

astballastshaft,theendmustbefoldedupagain.

ShortBallastTray(withsurfaceprotectionmats)

15

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

More informationonoursystemscanbefoundatourwebsite:

inthesolarareaunderDownloads.

INFORMATIONABOUTINTERNALANDEXTERNALGROUNDING

Theinternalbondingpathstartsatthemoduleandcontinuesviatheearthingpinintotheclampingpart

andcontinuesviathescrew,theassemblyclaw,themodulesuportandtheturn-inconnectortothebasic

profile.

Theexternalbondingpath mustbespecifiedbythe Installer.

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

16

COMPONENTSRECOMMENDEDBYSCHLETTERFOREQUIPOTENTIALBONDING

ILSCOGROUNDINGPATHINSTALLATIONINSTRUCTION

GBL-4SS, GroundLugInstallationInstructionsforPhotoVoltaicApplications

glass

moduleframe

stainlesssteel

hex nut

stainlesssteel

starwasher

deox

groundlug

GBL-4SS

stainlesssteel

flatwasher

stainlesssteel

splitwasher

stainlesssteel

hex bolt

sideview

frontview

17

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

Installer is responsible for and shall provide an appropriate method of direct

to-earth grounding according to the latest edition of the National Electrical

Code, including NEC 250: Grounding and Bonding, and NEC 690: Solar

Photovoltaic Systems." and "Installation shall be in accordance with CSA C22.1,

Safety Standard for Electrical Installations, Canadian Electrical Code, Part 1.

lGBL-4SSgroundlugperdiagram,use#10-32mountinghardware.

liberagh

notrequired,Schletterstronglyrecommendtheuseofconductorcompoundbetweenthemounting

surfacesinordertobetterprotecttheconnectioninallenvironmentalconditionsandpromoteconnection

longevity.

-4SS,apply35in-lbsmountingtorqueto#10mountingbolt.

liberalamountofconductorcompoundinwirewayofgroundlug

lgroundconductorinlugandtorquewirescrewtothe following:

6AWG:35in-lbs.

8AWG:25in-lbs.

10-14AWG:20in-lbs.

*Flatwasherandsplitwasherarenotrequired

AdditionalInformation:

ableforusewithflat-surfacedanodizedaluminumorgalvanizedsteeldesignatedG90

eptablemountinghole diameteris 0.196inches ±0.004inches (4.98mm±.1mm).

eptableframingmaterialthicknessisaminimumof0.062inches(1.57mm)to0.250inches

(6.35mm),with aflatsurfaceareofnolessthan 34by12mm(bottomofthe lug).

d to grounding holes (0.196'' ID) in anodized aluminum PV frame (0.062''-0.25'' thickness) with torque value 35

.” or equivalent.

d18mountingsystemistobeonlyincombinationwithlistedPV-modulesthatincludethespecific

otheapprovedmodulelistforthelistingPV-moduleswhich

canbeusedincombinationwiththeFixGrid.

ingofanEquipmentGroundingConductor(EGC),theratingoftheOvercurrentProtectionDevice

(OCPD)incircuitaheadoftheEquipmentshallnotexceedthevaluesinNECtable250.122wheretheEGCis

onlyrequiredtobelargerthanthecircuitconductorssupplyingtheequipment.

withaGroundingElectrodeConductor(GEC),thesizeoftheconductorshallcomplywithNEC

articles250.66forACsystemsand250.166forDCsystems.

aximumsystemovercurrentprotection(Cuconductor):

12AWG:

10AWG:

20A

30A

Thisrackingsystemmaybeusedtogroundand/ormountaPVmodulecomplyingwith

UL1703onlywhenthespecificmodulehasbeenevaluatedforgroundingand/or

mountingincompliancewiththeincludedinstructions.

18

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

OvercurrentProtectionDevice (grounding)

Accommodatedstrandedorsolidcopperwire(2gaugeto14 gauge).

Mustusebarecopperwiretoconnecttothegroundingwire,removeatleasttwoinchesofinsulation

toexposecopperwire.

Connectstothe bottom10railchannelofmodulerail.

Loosenorremovetopportion ofgroundinglogand insert

groundingwireintoappropriategroove.

Groundinglog(Part#135003-

003)

Groundingwiremustextend

throughgroundinglugbyatleast

1/4inch

Gauge of Grounding Wire Conductor

GENERALNOTESONMAINTENANCE

Yearlyinspectionofthesystemshouldbeconductedtomaintainoptimalperformancebyqualified

personnel.

Visualinspectionfor

signsofdamage

signsofwearofcomponents

signsofcomponents

positionofthe ballast

positionofroofprotectionmats

signsoflooseningofcomponents andfasteners

positionofroofprotectionmats

Replaceanyaffectedcomponents immediately:torqueatmoduleclamps mustbe

verifiedwith aTorquewrenchandshouldbesetat50%ofintendedtighteningtorque.

Donottouchthe livepartofthe wire,cable andconnectordirectlybutwith saferyequipment

(insulating tools)whennecessary.

WARNING!Contactyourinstallerimmediatlyifyoususpectyoursystemis notworking properly.

WARNING!ThePVSystemmustbeshutdownfirstifitneedsanyelectricalmaintenance.

Impropermaintenancemaycauselethalelectricshocks/orburns.

19

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

Fire Test

FixGrid racking system meet with Standard UL 2703, Clauses 11.1

that required a rack mounting system intended for stand-off, rack,

or direct mounting in combination with a specified roof, or

intended for integral mounting in combination with the specified

PV module(s) comply with the fire resistance requirements for a

“Class A” PV System Rating in accordance with the Standard for

Flat-Plate Photovoltaic Modules and Panels, UL 1703

.

•Fire Test Class A Type 1

•Fire class resistance rating: Class A when used with Type I

photovoltaic modules only

Fire Test configuration

INFORMATIONONTENSILEORSHEARSTRENGTH

Rapid16moduleclamps (accordingZ-14.4-631)

(available in 50 or 100mm lengths)

TENSILE

Profile

FixZ

FixZ

F

T

[kN]

3,88

1,63

MiddleClamps

EndClamps

SHEAR

Loaddirection:

16shearstrength[kN/clamp]

F

S

MiddleClamp

EndClamp

0,67

0,68

-INCONNECTOR

Maximumpermissiblepressure values

5400kPa

Maximumpermissibletensilevalues

2400kPa

20

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

APPROVEDMODULELIST

MANUFACTURERMODELNUMBERS

BVM6612

CS6X-P-FG

CS6X-P

CS6V-M

CS6U-P

CS6U-M

CS6U

CS6P-P-SD

CS6P-P

CS6P-M

CS6K-P-FG

CS6K-P

CS6K-MS

CS6K-M AB

CS6K-M

CS6K

CS5A-M

CS3W-PB-AG

CS3W-P

CS3W-MS

CS3W-MB-AG

CS3W

CS3U-PB-AG

CS3U-P

CS3U-MS

CS3U-MB-AG

CS3U

CS3L-P

CS3L-MS

CS3L

CS3K-PB-AG

CS3K-P

CS3K-MS

CS3K-MB-AG

CS3K

CS1Y-MS

CS1U-MS

CS1K-MS

CS1H-MS

ET-M660 290|285|280|275|270 WW|WB

ET-M672 340|335|330|325|320 BB

ET-M672 345|340|335|330|325 WW|WB

ET-P660 265|260|255|250 BB

ET-P660 270|265|260|255 WW|WB

ET-P672 315|310|305|300 BB

ET-P672 320|315|310|305 WW|WB

L-G2

L-G3

L-G4

DUO BLK-G5

DUO BLK-G6

DUO G6

DUO LG6

DUO-G5.X

DUO-G5

PRO L G4.1

PLUS L G4.2

PRO L G4.2

PLUS BFR G4.1

PRO BFR G4.1

BovietSolar

CanadianSolar

ETSolar

HanwhaQ

Cells

21

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

HanwhaQCells

(continued)

BLK G4.1/TAA

L G4.2 / 4.5

-G4.1|G4.1/MAX

BFR G4.1/ TAA or MAX

G4

L G4.1|G4.2

BFR G4|G4.1|G4.3|G4.4

G4

L G4.1

L G4.2

L G4.5

DUO BLK-G5/SC

DUO BLK-G6+

DUO BLK-G6+ /TS

DUO BLK-G6+/AC

DUO BLK-G6+/SC

DUO BLK-G7

DUO BLK-G8

DUO BLK-G8+

DUO G6+/AC

DUO L-G5

DUO L-G5.1

DUO L-G5.2

DUO L-G5.3

DUO L-G6

DUO L-G6.1

DUO L-G6.2

DUO L-G6.3

DUO L-G6.4

DUO L-G6.5

DUO L-G6.6

DUO L-G6.7

DUO L-G7

DUO L-G7.1

DUO L-G7.2

DUO L-G7.3

DUO L-G7.4

DUO L-G7.5

DUO L-G7.6

DUO L-G7.7

DUO L-G8

DUO L-G8.1

DUO L-G8.2

DUO L-G8.3

DUO L-G8.3/BFF

DUO L-G8.3/BFG

DUO ML BLK-G9

DUO ML BLK-G9+

DUO ML-G9

DUO ML-G9+

DUO XL-G9

DUO XL-G9.1

DUO XL-G9.2

DUO XL-G9.3

DUO-G5

DUO-G5/SC

DUO-G6

DUO-G6/SC

DUO-G6+

DUO-G6+/SC

DUO-G7

DUO-G8

DUO-G8+

DUO L-G5

DUO L-G5.1

DUO L-G5.2

DUO L-G5.3 B10B68:B138

22

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

Heliene

Heliene 36|60|72|96M

Heliene 36|60|72|96P

Heliene MAX HOMEPV Black 350

Heliene MAX Series 430

Helien 72 M G1

HyundaiSolar

HiS-M250|255|260|265RG HiS-

M310|315|320|325TI HiS-

S265|270|275RG

HiS-S330|335|340|345|350TI

Eagle 60|72

Eagle Black 60|72

Eagle MX JK07A|JK07B

Eagle PERC

JKM265PP-60

JKM270P-60-V

JKM275P-60

JKM275PP-60-V

JKM320P-72-V

JKM330P-72

JKM330PP-72-V

JKM390/395/400/405/410M-72HL-V

JKMxxxM-60HBL

JKMxxxM-72HL-TV

JKMxxxM-7RL3-TV

JKMxxxM-7RL3-V

KD260|265GX-LFB2

KU260|265|270-6MCA

KU260-6MCA

KU315|320-7ZPA

LGxxxN1C-A5

LGxxxN1C-G4

LGxxxN1K-G4

LGxxxN1W-G4

LGxxxN2C-B3

LGxxxN2W-A5

LGxxxN2W-B3

LGxxxS1C-A5

LGxxxS1C-G4

LGxxxS1W-G4

LGxxxS2W-A5

LGxxxN2T-A5

LGxxxN1T-V5

LGxxxN2T-V5

LGxxxQ1C-V5

LGxxxQ1K-V5

LGxxxA1C-V5

LGxxxN2T-J5

LGxxxN1C-V5

LGxxxN1K-V5

LGxxxN1C-N5

LGxxxN1C-A6

LGxxxN1K-L5

LGxxxN1K-A6

LGxxxQ1C-A6

LGxxxQ1K-A6

LGxxxN2W-L5

LGxxxN2W-E6

LGxxxN2T-E6

LGxxxN2T-L5

JinkoSolar

Kyocera

LG

23

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

Longi

LR6-60PE 300-320M

LR6-60HPH xxx M

LR6-72BP 355-375M

LR6-72HPH xxx M

LR6-72PH xxx M

LR4-72HBD 415-435M

LR4-72HBH 420-440M

LR4-72HBD xxx M

LR4-60HBD xxx M

LR4-72HPH/HIH xxx M

LR4-60HPH/HIH xxx M

LR4-60HPB/HIB xxx M

PS-M60

PS-M60(BF)

PS-M72

PS-M72(BF)

PS-P60

PS-P72

PS xxx P-20/U

PS xxx PH-20/U

PS xxx M-20/UH

PS xxx MH-20/UH

PEAK Energy Series REC245|250|255|260|265|270PE

PEAK Energy BLK2 Series REC245|250|255|260PE BLK2

TWINPEAK SERIES REC265|270|275|280|285TP

PEAK Energy 72 Series REC300|295 - 315PE

TWINPEAK REC330|335|340TP72

TWINPEAK 2 BLK2 SERIES RECxxxTP2 BLK2

TWINPEAK 2 SERIES

TWINPEAK 2S 72 Series RECxxxTP2S 72

REC Alpha - RECxxxAA

REC Alpha 72 - RECxxxAA 72

REC Alpha Black - RECxxxBlack

REC N-Peak-RECxxxNP

REC N-Peak-RECxxxNPBlack

REC TP2SM72-RECxxxTP2SM72

Twin Peak 3M - RECxxxTP3M

Twin Peak 3M - RECxxxTP3M Black

RSM60-6-270M-290M/5BB

PowerXT-400R-PM

PowerXT-400R-PM-AC

SunmodulePlus SW 275-290 MONO BLACK

SunmodulePlus SW 280-290 MONO BLACK (5-busbar)

SunmodulePlus SW 280-295 MONO

SunmodulePlus SW 285-300 MONO (5-busbar)

SunmodulePro-Series SW 260 POLY WOB

SunmoduleProtect SW 275-280 MONO BLACK

SunmoduleSW 100 POLY RGP

Sunmodule SW 150 MONO R6A

SunmoduleSW 150 POLY R6A

SunmoduleSW 320-325|340-350 XL MONO

SunmoduleSW 80 MONO RHA

SPR-X21-xxx-COM

STPxxxS –A60U/Wfhb

STPxxxS - A72U/Vfh

STPxxxS - A72U/Vnh

STPxxxS-24/Vfw

Philadelphia Solar

Phono Solar

RECSolar

Risen

Solaria

SolarWorld

SUNPOWER

Suntech

24

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

Talesun

FEATHER 2.0 TP660P

Hipro M295+ TP660M

Hipro M350+ TP672M

PID ZERO TP672M

TD660M

TD660P

TP660|672M

TP660|672P

TP660|672P(H)

TSM-xxx PA05.08

TSM-DE14A

TSM-DD14A

TSM-PD05

TSM-PD05.05

TSM-PD05.08

TSM-xxx DD05A.05(II)

TSM-xxx PD05.08

TSM-xxx PD05.10

TSM-PD14

TSM-PE14

TSM-PEG14

TSM-PEG40.07

TSM-PEG5

TSM-PEG5.07

TSM-DD06M.05(II)

TSM-DE06H

TSM-DE06M

TSM-DE15H

TSM-DE15M

TSM-DE18M

TSM-DEG06H

TSM-DEG06M

TSM-DEG15HC.20(II)

TSM-DEG15M.20(II)

TSM-DEG15MC.20(II)

TSM-DEG18MC.20(II)

TSM-PE06H

TSM-PE15H

TSM-PEG06H

TSM-PEG15H.20

Glacier Series G3

WP-xxxM/G3-60H-V (325|330|335|340PC)

Trina

WattPower

YingliGreenEnergy

YL260P|255P|250P|245P|240P-29b

YL275P|270P|265P|260P|255P|250P-29b

YL290D|285D|280D|275D|270D-30b

YL300C|295C|290C|285C|280C|275C-30b

YL325P|320P|315P|310P|305P|300P-35b

YL340D|335D|330D|325D|320D|315D-36b

25

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

ZNShine

ZXM6-60-xxx_M

ZXM6-H120-xxx_M

ZXM6-H144-xxx_M

ZXM6-HLD120-xxx_M

ZXM6-HLD144-xxx_M

ZXM6-HLDD144-xxx_M

ZXM6-LD60-xxx_M

ZXM6-LD72-xxx_M

ZXM6-LDD72-xxx_M

ZXM6-NH120-xxx_M

ZXM6-NH144-xxx_M

ZXM6-NHLD120-xxx_M

ZXM6-NHLD144-xxx_M

ZXM6-NHLDD120-xxx_M

ZXM6-NHLDD144-xxx_M

ZXP6-72-xxx_P

ZXP6-H144-xxx_P

ZXP6-HLD120-xxx_P

ZXP6-HLD144-xxx_P

ZXP6-LD72-xxx_P

26

FIXGRID SOUTH I I400338 I V3 I INSTALLATION GUIDE I 12-2020

SCHLETTER NA Inc. I SUBJECT TO CHANGE WITHOUT NOTICE

SCHLETTERNAINC.

520077CenterDriveSuite250

Charlotte,NC28217

Phone:+1704 595-4200

Fax:+1704 595-5210

CANADA:

Phone:+1519 946-3800

*****************************